Controls for aerobic treatment, UV disinfection and effluent dispersal — where the panel’s job is not just to run a pump, but to prove the treatment happened before anything leaves the tank.
A treatment system is only as good as the moment something fails. These panels supervise the parts that matter and hold the dose until treatment is proven.
A current relay proves the UV lamp is actually lit. A failed lamp locks out the dose instead of sending untreated water to the field.
Air and compressor supervision catch a failed blower or a lost air line — and hold the dose until air is back.
When the fault clears, the panel returns to service on its own. No truck roll just to press reset.
Smart and cyclic timers dose on a schedule the field was designed for, with timer-enable and override floats for real-world inflow.
Relay logic where it is enough, a PLC where it is not — each built to the sequence the system actually runs.
Float-called dosing with UV supervision and failsafe lockout.
Timed dosing with UV and air supervision; separate control feed stays live with the pump main off.
Time-dosed spray fields with a smart timer and UV supervision.
Two dosing pumps on a smart timer, alternated, with UV supervision.
Timer-based process control with current sensing and lockout on air or recirculation failure.
Programmable dosing and zone control for drip fields, where relay logic runs out.
Continuous aeration, UV lamp supervision and high-water annunciation for gravity-flow systems.
Residential and small commercial ATUs that must prove treatment before discharge.
Treated effluent dispersed by spray on a schedule.
Subsurface drip fields with dosing, flushing and zone control.
Systems designed to reduce nitrogen before it reaches ground or surface water.
Manufacturers who want a documented control panel under their own name.
We build production panels under our customers’ names — and we do not publish whose. The panels say enough:
Repeatable to the print, revision-controlled, and supported for the life of the panel — under your name, not ours.
Whatever the family, the same rules go into the box. That is what makes a panel built in Mims recognizable — to the inspector, to the service tech, and to us, years after it ships.
Every panel built and marked under the Listing, with a nameplate stating its own ratings.
Each unit carries its own serial and a build record. We know what is inside every panel we ship.
A code inside the door opens that panel’s current documents on any phone. No login, no searching.
The control assembly lifts out on quick-connects. Field terminations stay put while service happens on the bench.
Overloads, branch breakers and control fuses plotted together, so each device clears in its own zone.
Breakers, floats, clamps and weights we manufacture ourselves — so our lead times hold.
Tell us what the equipment has to do. We will engineer the control scheme, build it to UL 508A, and put your brand on the front if you want it there.