Simplex Pump Control Panel
Demand (float-controlled) simplex pump control · 120/240 VAC field selectable · 3-float or 2-float configuration. UL 508A Listed, file E547664. LE-4001 is the panel only; LE-4003 includes the float switch set.
A factory wire jumper powers the control circuit from L1 — the panel will not operate without it. Where a separate 120 V control-circuit feed is installed instead (jumper removed), THAT FEED STAYS ENERGIZED when the main feed is off — disconnect every feed and verify with a voltage tester before opening the panel. Ships configured 120 V (grouping pin between Terminal 2 and Neutral); remove the pin for 240 V and verify with a multimeter before energizing. A neutral is required even at 240 V — the control circuit operates at 120 V.
Documents
Quick Start Guide Operation Manual Specification Sheet Troubleshooting GuideAt a glance
- Models
- LE-4001 (panel only) · LE-4003 (with float set) — part numbers CP-001-4-0001 / 4-0003
- Voltage
- Dual 120/240 VAC single phase, field selectable by grouping pin — pin installed = 120 V (factory default), pin removed = 240 V
- Pump
- Single pump, up to 20 FLA — 1 HP @ 120 VAC or 2 HP @ 240 VAC
- Control
- 3-float demand control (On · Off · High Water) with R1 logic relay for full drawdown — field configurable to 2-float via grouping pins
- Alarm
- Red beacon + 85–95 dB buzzer · alarm test button · buzzer ON/OFF switch · alarm circuit limited to 5 A
- Protection
- 25 A MCB for pump + IEC contactor · 5 A MCB for the segregated control circuit. Overload protection is integral to the pump motor — there are no overload devices in this panel. High water is alarm only and never interrupts the pump.
- Supply circuit
- Minimum supply circuit ampacity 30 A (25 A pump branch + 5 A alarm & control circuit branch) · field-supplied main disconnect and feeder breaker
- Enclosure
- Type 4X polycarbonate, indoor/outdoor · body 10 × 8.4 × 5.2 in · overall 10.3 × 13.28 × 5.8 in incl. mounting flanges · approx. 7 lbs
- Compliance
- UL 508A Listed · file E547664