Control panel documentation

Aerobic Treatment Control Panel

CP-001-3-0006-240V

Time-based dosing · UV disinfection · failsafe lockout. 240 VAC pump circuit, 120 VAC control. UL 508A Listed, file E547664.

Read first — two power feeds

TWO separate feeds. The 240 V main powers only the spray/dose pump; a dedicated 120 V control circuit powers the air compressor, UV, alarms and timer — and it stays energized when the 240 V main is OFF. Disconnect BOTH and verify with a voltage tester before opening the panel. Neutrals from both feeds must land on the same neutral bus.

Documents

Operation Manual Installation, wiring, operation, SHT-13/2 schedule programming, PRI-51 supervision, troubleshooting, warranty · PDF Specification Sheet Ratings, protection matrix, float switch system · PDF

At a glance

Model
CP-001-3-0006-240V
Main power
240 VAC, 60 Hz, single phase — powers the spray/dose pump only
Control power
120 VAC dedicated feed — compressor, UV, alarm and timer
Spray / dose pump
240 V, up to 2 HP (20 FLA)
Compressor
120 V, ¼ HP (5.0 FLA) — panel rated ½ HP max
Timer
Elko SHT-13/2 Wi-Fi smart timer, with run-time hour meter
Protection
Air loss or UV fault locks out the spray/dose pump. The timer enable float blocks short doses. High water raises the alarm only — the pump stays on schedule by design.
Enclosure
Polycase ZH-100804 · NEMA 4X polycarbonate · 10.0 × 8.4 × 5.2 in
Compliance
UL 508A Listed · file E547664 · NSF/ANSI 40 compatible

Support & warranty

This panel is manufactured for AKHA Manufacturing, LLC. All technical support, warranty claims and service questions are administered by them.

Toll free 800-370-3749 · Phone (574) 936-2542